Abstract
Three-dimensional CFD simulations are carried out to investigate heat transfer and fluid flow characteristics of a four-row plain fin-and-tube heat exchanger using the Commercial Computational Fluid Dynamics Code ANSYS CFX 12.0. Heat transfer and pressure drop characteristics of the heat exchanger are investigated for Reynolds numbers ranging from 400 to 2000. Fluid flow and heat transfer are simulated and results compared using both laminar and turbulent flow models (k-ω) with steady and incompressible fluid flow. Model validation is carried out by comparing the simulated case friction factor (f) and Colburn factor (j) with the experimental data of Wang et al. [1]. Reasonable agreement is found between the simulations and experimental data. In this study the effect of geometrical parameters such as fin pitch, longitudinal pitch and transverse pitch of tube spacing are studied. Results are presented in the form of friction factor (f) and Colburn factor (j). For both laminar and transitional flow conditions heat transfer and friction factor decrease with the increase of longitudinal and transverse pitches of tube spacing whereas they increase with fin pitches for both in-line and staggered configurations. Efficiency index increases with the increase of longitudinal and transverse pitches of tube spacing but decreases with increase of fin pitches. For a particular Reynolds number, the efficiency index is higher in in-line arrangement than the staggered case.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.