Abstract

The aim of this study was to compare the measured effectiveness of an air curtain device at different jet velocities against a three-dimensional (3-D) computational fluid dynamics (CFD) model. The air curtain device was not as wide as the entrance and had a geometry that encouraged 3-D flow. By carefully setting up the air curtain an effectiveness of 0.71 was achieved compared to the initial value of only 0.31 as set by the air curtain device installer. The 3-D CFD model predicted the infiltration through the entrance with no air curtain to an accuracy of within 20–32%. The predicted effectiveness, E, of the air curtain at different jet velocities was 0.10–0.15 lower than measured. The shape of the effectiveness curve against jet velocity was well predicted. CFD has shown that the flow from this air curtain cannot be considered as 2-D. The central part of the jet is deflected away from the cold store by the Coanda effect caused by the air curtain device’s fan body. The edges of the jet are deflected into the cold store by the stack pressures and turn into the void caused by the deflected central jet.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.