Abstract

A large-scale pulsed MHD generator with an MHD channel of 4.5 m, having demonstrated the maximum electric power output of 510 MW, is studied numerically with a time-dependent three-dimensional analysis. It is shown that strong oblique shock waves are generated at a connection between the nozzle and insulating walls, traveling to the channel exit. The strong oblique shock waves cause fluctuations of gasdynamic quantities along the x-direction, resulting in a slight decrease of the Faraday current density. As a result, the strong oblique shock waves deteriorate slightly the generator performance. It is also shown that a strong pseudo-shock wave with a large boundary-layer separation is induced by the strong MHD interaction under the condition of a low channel voltage. The boundary-layer separation becomes large near the anode because of the strong Lorentz force in the y-direction attributed to the large Hall current. It is also shown that the cross-sectional secondary flow attributed to the Hall current on the y– z plane is not induced under the present conditions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.