Abstract

The source resistances for surface voltages (touch, transferred and step voltage) are considered. It is proved that the source resistances of the touch and transferred voltages are the same, given by the grounding resistances between the feet of a human and the grounding system. In a practical situation, however, this resistance is very close to that of the ANSI/IEEE Standard 80 that is widely accepted. The source resistance of the step voltage is simply the resistance between the two feet, not at all perturbed by the grounding system. Proofs are derived rigorously by combining the field Galerkin's moment method and basic circuit theory.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.