Abstract

To avoid global warming potential gases emission from vapor compression air-conditioners and water chillers, alternative cooling technologies have recently garnered more and more attentions. Thermoelastic cooling is among one of the alternative candidates, and have demonstrated promising performance improvement potential on the material level. However, a thermoelastic cooling system integrated with heat transfer fluid loops have not been studied yet. This paper intends to bridge such a gap by introducing the single-stage cycle design options at the beginning. An analytical coefficient of performance (COP) equation was then derived for one of the options using reverse Brayton cycle design. The equation provides physical insights on how the system performance behaves under different conditions. The performance of the same thermoelastic cooling cycle using NiTi alloy was then evaluated based on a dynamic model developed in this study. It was found that the system COP was 1.7 for a baseline case considering both driving motor and parasitic pump power consumptions, while COP ranged from 5.2 to 7.7 when estimated with future improvements.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.