Abstract
An irreversible variable-temperature heat reservoir four-temperature-level absorption refrigeration cycle model is established in this paper. The considered losses include heat resistances between heat reservoirs and working fluid, internal irreversibilities due to internal dissipation of the working fluid, and the heat leakages between the heat reservoirs and the surroundings. The general relationships between the cooling load and the COP are derived. Besides, the optimal performance characteristics between the cooling load and the COP are obtained using numerical examples. The effects of heat resistances, internal irreversibilities, heat leakages, and the thermal capacitance rates of heat reservoirs on the cycle performance are analysed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.