Abstract

Cogeneration turbines operate in different operation modes that considerably differ as to the working process conditions. In summer time, when heat demand is minimal, almost all steam flow passes through all turbine stages and enters into the condenser (condensing mode of operation). When heat supply is needed, the steam bleed-offs are used. The several last stages of the turbine (low-pressure part—LPP) have a control diaphragm at the inlet. When the heat supply is large, the diaphragm is maximally closed, and the entire steam flow, with an exception for a minimal ventilation flow is delivered to the steam bleed-offs (cogeneration mode). LPP flow path is designed for the optimal operation in the condensing mode. While running in cogeneration mode, the LPP operating conditions are far from optimal. Depending on the ventilation steam flow rate and outlet pressure, the LPP power can drop to zero or even become negative (ventilation mode). It is proposed to control an outlet steam pressure by using the heat pump that operates with steam. The heat pump energy consumption can be compensated and even exceeded by optimizing the steam expansion process in LPP. In this respect, operating conditions of cogeneration turbine LPPs during the cold season are analyzed. A brief description of a heat pump operating with steam is made. The possibility of increasing cogeneration turbine efficiency by using a steam heat pump is shown.