Abstract

In order to increase the magnetic field and temperature margin of superconducting magnets, a test facility for a 3K sub-cooled helium refrigerator was proposed to decrease the operation temperature from the saturated helium to the sub-cooled helium. The process flow of 3K sub-cooled helium refrigerator has been analysed, including the 4.5K refrigerator unit and 3K refrigerator unit. Two cold compressors arranged in series have been adapted to decompress pressure to achieved 3K sub-cooled helium. The thermodynamic cycle of the 3K sub-cooled helium refrigerator have been designed, which can provide 2.5kW@4.5K in 4.5K mode or 1.2KW@4.5K + 700W@3K in 3K mode. As the most important port, the design parameters and mechanical test at normal temperature test of cold compressors were shown.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.