Abstract
A thermodynamic analysis of a hybrid geothermal heat pump system is carried out. Mass, energy, and exergy balances are applied to the system, which has a cooling tower as a heat rejection unit, and system performance is evaluated in terms of coefficient of performance and exergy efficiency. The heating coefficient of performance for the overall system is found to be 5.34, while the corresponding exergy efficiency is 63.4%. The effect of ambient temperature on the exergy destruction and exergy efficiency is investigated for the system components. The results indicate that the performance of hybrid geothermal heat pump systems is superior to air-source heat pumps.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.