Abstract
This paper presents a numerical investigation on a heat transfer enhancement by using a computational fluid dynamics software. The heat transfer enhancement is implemented by inserting twisted tape into a heat exchanger tube. The twisted tapes with twist ratios of 4, 6 and 8 were modified with alternate axis. The pitch of the twisted tape having the rotation direction such as clockwise and counterclockwise are connected with 90º connection angle. Water is selected as working fluid and turbulent flow condition corresponding to Reynolds number ranging from 5000 to 29000 are considered in the study. The heat exchanger tube is under constant heat flux of 50 kW/m2. Numerical analysis results prove that the use of twisted tape improves thermal performance compared to smooth tube. As the twist ratio increased, the heat transfer performance and the friction loss penalty decreased. Overall results are determined with thermohydraulic performance criteria (THP). The highest THP value is obtained as 1.21 for the tube inserted with the twisted tape which has the twist ratio of 4 and alternate axis between the twist pitches at Reynolds number of 5913
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.