Abstract
Natural draft direct dry cooling system (NDDDCS) uses the natural draft dry-cooling tower instead of axial flow fans, so can effectively reduce the power consumption, operating costs and also the noise caused by fans. In this work, two types of NDDDCS with horizontally arranged heat exchanger bundles (HAHEBs) and vertically arranged heat exchanger bundles (VAHEBs) are proposed respectively. Furthermore, the cooling delta apex angles from 60° to 180° are further investigated. The air-side velocity, pressure and temperature fields are presented and the heat rejections for various configurations of NDDDCS are calculated and compared. The results show that the cooling performance of NDDDCS with VAHEBs is superior to that with HAHEBs in any case, especially at high wind speeds. The VAHEBs with the apex angle of 150° have the best cooling performance, so can be recommended in the potential practical engineering of natural draft direct dry cooling system in power plants.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.