Abstract

Interference-fit finned tubes depend for their heat-transfer capability upon a contact pressure between fin and tube. The bond resistance under such conditions is relatively small compared to the other resistances in the heat-flow path. At elevated temperatures, however, differential thermal expansion between fins and tubes completely relaxes the contact pressure and introduces an additional gap resistance; this may become a significant part of the total resistance to heat transfer. A theoretical method for predicting the gap resistance is derived in terms of the fin and tube dimensions, their physical properties, the fluid temperatures and heat-transfer coefficients, and the initial contact pressure. Test data on five finned-tube units representing embedded, tension-wound, and muff-type fins are given in graphical and tabular form. Very good agreement is found between theory and test in two of the interference-fit units. The other two show only fair agreement.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.