Abstract
Thermal response test (TRT) is becoming increasingly popular in obtaining the ground thermal properties as well as evaluating the performance of the ground heat exchanger (GHE) that determines the properties of ground source heat pump (GSHP) system. This study investigated a practical engineering project, which is located in Shijiazhuang, Hebei Province, as an example to test the ground thermal properties. A popular constant heating-flux method (CHFX) was used with the heat load of 3.6kW and 8.4kW, respectively. This investigation compared and analyzed the ground thermal properties by the line source model (LSM) and the cylinder source model (CSM). This study also conducted the sensitivity analysis on different data intervals by fixing starting time or ending time. Moreover, a new method (Bland–Altman analysis) was proposed to analyze and determine the agreement between simulated and experimental data. The results showed that the new method performed well in evaluating the agreement and could help to properly choose the test duration and data interval for thermal response test.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.