Abstract

Interruption tests were conducted using the same circuit breaker for an initial pressure of SF6 0.5 MPa (gauge pressure) and CO 2 mixture 1.0 MPa, 0.8 MPa, and 0.6 MPa. The pressure-rises in the compression and thermal expansion chambers were measured for verifying the computational results using a simplified synthetic test facility. Further, the possibility of the CO 2 mixture substituting SF 6 gas was confirmed. Moreover, in view of the thermal recovery capability, it has also been confirmed that the pressure of the CO 2 mixture can be reduced almost to the same value as that of the SF 6 gas by optimizing the design parameters of the interrupter.