Abstract
Artificially roughened solar air heaters have been analysed (Prasad and Saini, 1988) for fully developed turbulent flow and found to perform better both quantitatively and qualitatively compared to the smooth ones under the same operating conditions. Optimal thermo-hydraulic performance of such solar air heaters has been analysed (Prasad and Saini, 1991) and investigated (Prasad and Verma, 2000) for the maximum heat transfer and minimum pressure drop.This paper represents the experimental results on heat transfer and thereby thermal performance of artificially roughened solar air heaters for fully developed turbulent flow data collected under actual outdoor conditions. Such solar air heaters have been found to give considerably high value of collector heat removal factor (FR), collector efficiency factor (F′) and thermal efficiency (ηth) as compared to the corresponding values of those of smooth collectors. In the range of the operating parameters investigated, the ratio of the respective values of the parameters FR, F′ and ηth for the roughened collectors to the smooth collectors have been found to be 1.786, 1.806 and 1.842 respectively.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.