Abstract

Due to high heat flux generation inside microprocessors, water-cooled heat sinks have gained special attention. For the durability of the microprocessor, this generated flux should be effectively removed. The effective thermal management of high-processing devices is now becoming popular due to high heat flux generation. Heat removal plays a significant role in the longer operation and better performance of heat sinks. In this work, to tackle the heat generation issues, a slotted fin minichannel heat sink (SFMCHS) was investigated by modifying a conventional straight integral fin minichannel heat sink (SIFMCHS). SFMCHSs with fin spacings of 0.5 mm, 1 mm, and 1.5 mm were numerically studied. The numerical results were then compared with SIFMCHSs present in the literature. The base temperatures recorded for two slots per fin minichannel heat sink (SPFMCHS), with 0.5 mm, 1 mm, and 1.5 mm fin spacings, were 42.81 °C, 46.36 °C, and 48.86 °C, respectively, at 1 LPM. The reductions in base temperature achieved with two SPFMCHSs were 9.20%, 8.74%, and 7.39% for 0.5 mm, 1 mm, and 1.5 mm fin spacings, respectively, as compared to SIFMCHSs reported in the literature. The reductions in base temperature noted for three SPFMCHSs were 8.53%, 9.05%, and 5.95% for 0.5 mm, 1 mm, and 1.5 mm fin spacings, respectively, at 1 LPM, as compared to SIFMCHSs reported in the literature. In terms of heat transfer performance, the base temperature and thermal resistance of the 0.5 mm-spaced SPFMCHS is better compared to 1 mm and 1.5 mm fin spacings. The uniform temperature distribution at the base of the heat sink was observed in all cases solved in current work.

Highlights

  • The minimum heat transfer rate observed in three slots per fin minichannel heat sink (SPFMCHS), with 1.5 mm fin spacing, was 280 W at 0.5 LPM

  • The heat sinks with two SPFMCHSs showed a higher heat transfer as compared to three SPFMCHSs with varying LPM and fin spacings

  • The base temperature recorded in two SPFMCHSs with 0.5 mm, 1 mm, and 1.5 mm fin spacings at 1 LPM was 42.81 ◦ C, 46.36 ◦ C, and 48.87 ◦ C, respectively, which is 9.20%, 8.74%, and 7.39% lower than the reported values in the literature [1] for straight integral fin minichannel heat sink (SIFMCHS)

Read more

Summary

Introduction

With the rapid development in the information technology sector, the thermal management of electronic devices is becoming essential due to the high generation of heat flux. The world is advancing rapidly towards compact devices; this presents the challenging task of the effective and timely removal of unwanted heat. This problem has attracted many researchers to create efficient cooling techniques while avoiding any losses in functioning of the devices. Air was used for the removal of heat from the electronic devices, but it is unable to remove high heat fluxes. Attention is being focused upon liquid cooling techniques, due to their higher efficiency when compared to air

Methods
Results
Conclusion
Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call