Abstract

An experimental study was carried out to investigate flow-induced vibration, heat transfer and pressure drop of helically coiled tubes of an intermediate heat exchanger (IHX) for the HTTR, using a full-size partial model and air as the fluid. The test model has 54 helically coiled tubes separated into three layer bundles, surrounding the center pipe. The vibration of the tube bundles was mainly at the center pipe, and the individual vibrations of the tube bundles were not significant under the operation conditions of the IHX. The heat transfer of the tube outside, due to forced convection, was obtained as a function of Re 0.51Pr 0.3, and the friction factor, depending on the tube arrangement, was proportional to Re −0.14.