Abstract
In Singapore's industry, the required temperature of a district cooling system's outlet and return water are 5 °C and 12 °C, respectively. Thus far, few researches have been reported on the cascaded phase change material (PCM) tank focusing on this temperature duration. In this study, a cascaded packed-bed tank for a district cooling system is proposed to improve heat transfer efficiency and decrease tank cost with the same cold energy capacity. The cascaded PCM system, employing PCM-1 and PCM-2 (volume ratio 50%–50% and 30%–70% tetradecane-hexadecane mixtures), is designed, modeled, and validated through experimental data. Key results revealed that the PCM-1 tank performs poorly during its charging phase, while the PCM-2 tank performs poorly in discharging phase. However, the proposed cascaded packed-bed tank that simultaneously PCM-1 and PCM-2 can achieve high average exergy efficiencies during the charging and discharging phases. Additionally, the cascaded system incorporating 0.42 of PCM-1 and 0.18 of PCM-2 demonstrates higher exergy efficiency and tank volume but incurs higher construction costs than other tank designs. Comparatively, the same cold energy capacity tank with 0.18 of PCM-1 and 0.42 of PCM-2 reduces construction cost by 6.8%, with a depreciation of exergy efficiency by 14.1% during the discharging phase.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.