Abstract

This study aimed to assess thermal comfort for workers in three buildings for wet coffee processing in Colombia, using the WBGT index, and temperature and relative humidity analysis through mapping. The limits recommended by the WBGT index were exceeded during the activity of putting fuel in the dryer in Building 3. The three buildings presented spatial hygrothermal variability due to the coffee dryer, as well as problems with ventilation, volume control, and the thermal resistance of materials in Buildings 2 and 3. In order to favor heat transfer from the dryer to the outside environment, and to make the thermal environment of these buildings more homogeneous, it is recommended to install thermal bridges around this area, to make more efficient the evacuation of steam and heat, as well as to increase the natural ventilation area in Buildings 2 and 3, and install ventilation skylights over the dryer.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.