Abstract
Research to determine the relationship between current load and temperature rises in shielded and reeled coal mine trailing cables is discussed. Temperatures within and on the cables were measured with thermocouples and the data recorded over time by computer. Steady-state DC load tests with two type SHD-GC cables revealed that only 3 to 7% more current than the Insulated Cable Engineers Association (ICEA) ratings for shielded cables was required to reach rated insulation temperature. The ability of the metallic shielding to absorb heat was reflected in longer thermal time constants than with unshielded designs. Steady-state temperature rises were monitored in a two condition unshielded, flat cable wound on a shuttle car cable reel. Stabilized axial temperature profiles exhibited maxima midway between the reel flanges. Static derating factors, expressed as percentages of open-air ampacity, were considerably less than ICEA ratings for reeled cables. The findings support a tentative contention that deratings for trailing cables wound on reels should be based on the specific cable configuration. >
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.