Abstract
AbstractThis paper reports the computational results of an investigation of oil storage tanks with the shape of an open cylindrical shell under thermal loads induced by fire. Interest in this problem has arisen as a consequence of a catastrophic fire that affected an oil storage facility in Puerto Rico in 2009 that caused the failure of 21 large tanks. To identify patterns of deformations that could be expected under various fire conditions, computer modeling has been carried out for one tank geometry. It is assumed that fire occurs outside the tank and induces an increasing temperature field affecting part of the external surface in the circumferential direction. The nonlinear shell response is modeled using finite elements under thermal loads and self-weight. The nonlinear behavior is computed to identify thermal buckling of the shell as a limit point. The response is initially computed for empty tanks, and the influence of various factors is investigated, including the liquid stored, a temperature grad...
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.