Abstract
The dynamic management of electric power distribution lines has become a topic of great interest at present. Knowledge of the ampacity of cables is fundamental to carrying out dynamic management. In this study, the ampacity of buried cables in different soil resistivities and depths was calculated. A small-scale model was built in the laboratory to simulate the operating conditions of a buried cable. With the experimental results, a numerical model based on the finite element method was validated to evaluate the ampacities calculated by two standards. A comparison was made between the ampacities calculated from the IEC 60287-1 and UNE 211435 standards and those obtained from the simulated model. In addition, a comparison was made regarding the steady-state temperatures obtained at each calculated ampacity. The results obtained from the simulated model design show that the ampacity calculation method of the IEC 60287-1 standard where drying-out of the soil occurs is the most accurate, and has the least risk of exceeding the maximum permissible cable temperature.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.