Abstract

In the present work, the thermo-fluid characteristics of a heat exchanger formed of helical coiled tubes immersed in cold water are investigated experimentally. Two types of helical coiled tube are tested, a conventional vertical single helical coiled tube and a new triple vertical helical coiled tube in parallel connection called as meshed coils. The effect of hot water flow rates inside the tubes (ranges from 2.67 to 7.08 l/min), and its inlet temperatures (namely 50, 60, 70 and 80 °C) are investigated. The experimental results show that increasing the flow rate inside the meshed coils leads to decrease the temperature difference between inlet and outlet. An enhancement of heat transfer for meshed coils compared to single coil has been noticed. Higher effectiveness is obtained for meshed helical coils from \({\varepsilon}\)-NTU relation in comparison with the single helical coiled. The pressure drop for the new tested coils is found lower than that for single coil (reaches 86 % at Re no. equal to 12,072), which leads to a considerable saving in power required for pumping.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call