Abstract

A pool fire test was conducted in an uninsulated steel container under low ambient temperature condition, at −20°C. The heat balance of the enclosure fire was analyzed. The size of the container was 12 m× 2.4 m and 2.4 m high, and it was made of 3-mm-thick steel. During the fire test, the fuel mass loss rate was recorded and the temperatures at different positions were measured with high-temperature thermocouples and plate thermometers. The fire scenario was simulated by using fire dynamics simulator software, and the simulated and measured results were compared. The coarse high-temperature thermocouple responded slower, and therefore, temperature measured by the high-temperature thermocouple was corrected to eliminate the effect of the thermal inertia. Furthermore, a simple two-zone model was proposed for estimating gas temperature in the enclosure of the highly conductive steel walls assuming a constant combustion rate. The convective and radiative heat transfer resistances at the inside and outside surfaces of the enclosure were analyzed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.