Abstract

A mechanical pre-cooling auto-cascade refrigeration (PACR) system was proposed, R600a single-stage vapor compression system was used to provide pre-cooling for R600/R170 auto-cascade refrigeration (ACR) system. Performance of PACR system under different operating conditions was discussed. The result showed that maintaining a constant outlet temperature of 30°C for the condenser and −45°C for the evaporator in a PACR system resulted in an optimal intermediate temperature that maximized coefficient of cooling performance (COP). At this time, the optimal intermediate temperature of R600/R170 was 0°C, the COP maximum value ( COPmax) was 0.693 and exergy efficiency ( ηEx) was 20.9%. And as the evaporator outlet temperature decreases to −70°C, the optimal intermediate temperature decreases to −10°C. The cooling capacity ( Qe) of the low-temperature grade circulating refrigerant in the PACR system using R600/R170 at different evaporation temperatures was increased by 86.3%–108% compared to that of R134a/R23. COPmax was increased by 7.1% compared to that of R134a/R23 at the evaporator outlet temperature of −60°C.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.