Abstract

The model of solution heat exchangers of mixed absorption refrigeration cycle was developed. The effects of strong solution temperature difference between inlet and outlet of solution heat exchanger on the coefficient of performance (COP) and cooling water flow rate of mixed absorption refrigeration cycle were analyzed, at the same time, the effects of temperature difference on the unit heat exchange area of counter-flow and cross-flow solution heat exchangers were analyzed. The theoretical analysis results showed that there was an optimal value for the strong solution temperature difference, for the mixed absorption system, the optimal temperature difference was about 12°C, the corresponding COP was 11.2% higher and the cooling water flow rate was 7.8% less than that of system without heat exchanger.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.