Abstract

A distributed parameter method has been established for a ground-source heat pump in this paper, with this model, the working process of this heat pump system was simulated. The results agree well with experimental data and show that heat-capacity and COP increase when the cooling water flow rate in the tube-in-tube heat exchanger increases; heat-capacity decreases when the temperature of inlet water of the tube-in-tube heat exchanger rises; COP, between 3.8 and 4.5, is higher than that of conventional air-source heat pumps.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.