Abstract

The single control valve closure in fast (SCVCF) event is the most limiting transient in terms of delta critical power ratio (ΔCPR) for the Lungmen Plant, which is a basis to determine the operating limit minimum critical power ratio value. The partial arc mode is adopted in Lungmen Plant to control the position of the turbine control valve. However, the transient analyses presented in the Lungmen Final Safety Analysis Report (FSAR) assume that the TCVs are in the full arc mode. In this study, the Lungmen RETRAM model with partial arc mode is used to analyze the SCVCF event to offer more realistic results than the FSAR. It is concluded that the most limiting maximum combined flow limiter (MCFL) setting in RETRAN analysis is different from that of FSAR. An optimum operating range for the MCFL is suggested to gain the margin against the operating drift. Additionally, a Heat Flux Factor index is defined to appropriately determine the ranking of these cases in terms of ΔCPR.