Abstract
The smart distribution system is an important aspects of the smart grid framework. There will be systematic update on the infrastructure of distribution side. In smart distribution grid pilot cities of China, a large number of ring main units are installed to improve the system reliability and there will be higher DG penetration rate to realize emission control. Therefore, the short circuit currents on the distribution side in the smart grid framework will be higher than that in the conventional distribution system. To meet this challenge, the fast short circuit current limiter (Is-limiter) is proposed to reduce the short circuit current level. The first 10kV Is-limiter has been installed in Xiamen. The aim of this paper is to study the impact of the Is-limiter on the distribution system in terms of short circuit current level, voltage quality and DG dynamic performances. In this paper, formula to describe the short circuit current level and the voltage sag level in the Is-limiter embedded network are deduced and the DG dynamic performances during fault are studied by time domain simulation. It is expected that the research in this paper can provide references for employing Is-limiter.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.