Abstract
In order to effectively suppress the noise radiation from large electrical power transformers, both the structure-borne and air-borne sound fields need to be characterised. The characterisation can be made either from theoretical predictions or by in-situ measurements. This paper presents the study of the sound radiation from a large power transformer in a substation. The radiation pattern can be predicted from the measured acceleration distribution and the predicted value is not affected by other noise sources. Alternatively, the farfield sound pressure level can be predicted from the sound pressure level measured at NEMA locations. Both the near- and far-field power radiation can be in-situ measured using the sound intensity technique. It is shown that both the vibration of a transformer tank wall and the radiated noise consist of a series of tonal components mainly at the first few harmonic frequencies of 100 Hz. Also, the neglect of the noise radiation from the transformer (top and bottom) lids does not affects the accuracy of the transformer radiation characterisation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.