Abstract

According to IEC60060-1, IEC60060-2 requirements, the large transformer should take impulse voltage test in site. However, this test is not performed in the field for the impulse voltage generator huge and difficult to operate. To solve this problem, IEC60060-3 propose using oscillating impulse voltage for equipment on-site impulse withstand voltage test. Oscillating impulse voltage has higher generation efficiency and close to the actual voltage waveform that electrical equipment bear. For the transformer, the oscillating impulse voltage can generated through inductive method. In order to study the generation of oscillating impulse voltage through inductive method for transformer, the simulation circuit is established using ATP soft and the oscillating switching impulse voltage characteristics is studied in this paper. The result show that the oscillating switching impulse voltage waveform that accordance with IEC requirements can be generated through inductive method for transformer.