Abstract

The paper analyses a kind of technology and products of ideal and normal non-contact electromagnetism tap changer, poses the calculating formula of circulating current. It is easy to control with the project of normal tap changer technology, but in this case the transition resistances and reactors need to be used, and the circulating current will appear when the tap position is changed. It will lead to electricity dropping, so the performance is not good. There is the accurate test technology of current zero and voltage zero in the project of tap changer technology based on intelligent module MCT801A, the high power current limiting resistances or reactors will not be used, the current can be continuous without impact, over-electricity or electricity dropping phenomena when the tap position is changed, the waveform of computer simulation and the waveform measured exactly of voltage and current are provided by the paper when the tap position is changed ideally, It will have positive significance on On-Load Tap Changer (OLTC) study of the Smart Grid.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.