Abstract

This article presents the results of a theoretical study of the infl uence the outside air infi ltration through the enclosing structures of the walls on the amount the air’s exchange in low-rise residential buildings. Based on the information analysis from offi cial documents of state statistical and analytical bodies, the most frequently used external wall structures in modern low-rise residential construction have been determined. Based on the provisions analysis of modern regulatory documents in the construction’s fi eld, the minimum values the required air exchange were determined and the calculations of the values the infi ltration air fl ow through the outer walls for various premises of low-rise residential buildings were made. Based on the results of the analysis and calculations was made a generalizing conclusion that for the considered premises of modern low-rise residential buildings, at the expense of the infi ltration of outside air through the enclosing structures of the walls, it is impossible to provide even 20 % of the minimum air exchange.