Abstract

In order to predict the usefulness of ultrasonic techniques for detecting and locating transformer coronas or partial discharges, it is necessary to determine the relationship between electrical and ultrasonic values of different coronas within an unobstructed oil environment. Experiments are reported in which typical corona sources, ranging in value from ~5-~105 pC, were energized within an oil-filled transparent tank and the ultrasonic emissions recorded via a transducer on the tank outer wall. Several distinct modes, changing with magnitude, of the oil discharges were observed, and the relationship between charge measurements Q and ultrasonic values P were found to vary from P ∝ Q <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">1/2</sup> to P ∝ Q.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.