Abstract
This paper represents the polarization and depolarization current (PDC) of the natural ester stressed by partial discharge (PD). The needle-plane electrode was used to simulate corona discharge in natural ester. Besides, the needle electrode as a high voltage electrode placed on the 8 hours natural ester impregnated pressboards and the plane electrode as a grounded electrode were used to simulate the surface discharge. To simulate the internal discharge, the plane-plane electrode inserted with various condition impregnated pressboards were experimented. PD phenomena were simulated in the natural ester container for 1, 3, and 6 months. Then the PD-stressed natural ester was used as the liquid specimen for polarization and depolarization current measurement. It was found that the PDC characteristics of natural ester undergone with various PD types were obviously different.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.