Abstract

Serious consideration is being given to large power-system interconnections which could develop short circuits at certain locations in excess of 3,500,000 kva. High-voltage oil-circuit-breaker capabilities for such heavy duty are reviewed in this paper, the fundamental design requirements outlined, and results of high-power laboratory tests presented which demonstrate that interrupting capacity ratings as high as 5,000,000 kva are feasible. Laboratory test methods for demonstrating these extremely high arc rupturing ratings are evaluated. The importance of verifying high-speed reclosing performance with high-power tests is emphasized, and on the basis of data already obtained, standard reclosing time intervals considerably less than 20 cycles are foreseen.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.