Abstract

In recent years, more and more transformers are designed with low induction levels and improved core designs. That leads to a change in the contribution hierarchy of the sound sources in transformers. According to the IEC Power transformer standard, the decision as to whether it is significant to perform load current sound measurements is made on a single equation which depends only on the rated power. In this paper we shall suggest, through test examples, that this equation can be misleading and a modified methodology which is based on measurements of noise at both �no-load� and �load� states, is necessary.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.