Abstract

An experimental method of determining the axial forces in power transformers is applied to a transformer constructed so that various tapping arrangements can be set up, and curves are given of the forces which occur with typical methods of tapping concentric windings.It is considered that the simple “residual ampere-turn” method of calculating axial forces is sufficiently accurate for design purposes, and a number of formulae are given which should cover most of the requirements of the transformer designer.The distribution of axial force around the periphery of the coils is investigated experimentally.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.