Abstract

A vertical countercurrent water–air heat and moisture exchange tower attached to a main fan diffuser is designed. To reduce water loss blown away by the airflow from the exchange tower, the forces acting on droplets are analysed. Droplet motion may be classified under four conditions: (1) downward initial acceleration; (2) upward initial acceleration; (3) droplet blown away by airflow; (4) droplet suspension. With droplet break-up neglected, a general equation for the maximum droplet drop-height is presented and numerical calculations are performed. Equations for the maximum drop-height under Conditions 3 and 4 are deduced, and the equation for Condition 3 is applied to an engineering case study. The effect of air velocity on the maximum drop-height is more significant than that of other factors. The conclusions provide a novel approach to optimizing the design of vertical countercurrent water–air heat and moisture exchange towers attached to main fan diffusers.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.