Abstract
The topology of a power grid network is a piece of critical information for power grid operations. Different power grid topologies can change grid characteristics, inter-area oscillation modes, mode shapes, and even the robustness of the power system. This paper presents some preliminary study results, based on an approved WECC operating case and a modified low damping WECC system, to show the impact of topology changes resulting from N-1 contingencies on power system modes and mode shapes. The results show that topology changes can have very different impact on modal properties in a power system: some result in an unstable situation, while others can improve small signal stability. For the former, the studies show about a 4.5% damping reduction, so a 5% damping margin would be required to ensure the system can sustain the contingencies. For the latter, those topology changes could be used as a control method to improve small signal stability. Mode shapes normally do not change when there is an N-1 topology change. These observations suggest that the inclusion of topological information is useful for improving the accuracy and effectiveness of power system control schemes.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.