Abstract

We have investigated the influence of surface charges on the discharge development across particle contaminated spacer surfaces under SF/sub 6/ for lightning impulse (LI) voltages (1.2/50 /spl mu/s). Surface charges may be generated by dc, ac or lightning impulse stress. The discharge characteristic shows a strong reduction of the insulation strength if the applied voltage and the surface charge have opposite polarities. The investigations were performed with a needle protrusion attached to the bottom electrode to give severe field distortion. The bottom electrode was biased positively. The influence on the discharge process is observed by measuring the surface charge distribution and predischarge currents. The results reveal changes in streamer onset voltage, streamer to leader transition, and leader development.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.