Abstract

Frequency Response Analysis (FRA) is a test method used for assessment of mechanical condition of transformer active parts. Its biggest problem is the interpretation of test results, namely the relationship between scale of differences between compared curves and the decision for further operation of the given transformer. Very often visible differences between two FRA curves do not mean that there is a deformation in the winding. The cause of the curve shift may come from other elements of the transformer that influence inductive or capacitive parameters. This paper takes under consideration the influence of both capacitance and inductance changes on transformer frequency response (FR). The analysis is performed with the computer model of a transformer and also some experimental results are presented, showing the influence of capacitance and inductance changes on the FR of real transformers. The results of research showed that this influence may lead to misleading effects on the shape of FR characteristics. The paper presents an analysis that can be used in the assessment of FRA measurement, especially in the case of uncertain data comparison results.

Highlights

  • Transformers play a major role in power distribution systems

  • Frequency Response Analysis (FRA) is a test method used for assessment of mechanical condition of a transformer active parts

  • Visible differences between two FRA curves recorded for the same winding over time do not mean that there is a deformation in the winding

Read more

Summary

Introduction

Transformers play a major role in power distribution systems They are expected to be in operation for at least 30 years, sometimes even in very unfavorable conditions. One of the key values in power distribution is availability, as its increased value over longer timespans translates into less total distribution costs for operators and an increase in the volume of energy sales. When it comes to older units, owners often have to decide whether to further operate them with some technical restrictions, schedule major maintenance, or withdraw the from further operation and replace them with new units. Comprehensive measurements, give users detailed information about the transformers actual technical state, and using this information the operator can decide if any actions should be taken in the future

Objectives
Methods
Results
Conclusion
Full Text