Series capacitors compensation plays a more and more important role in long-distance and large-capacity transmission system, whose model has a significant impact to system stability study. Firstly, both gap protected SC model and linearized model is applied into the available power transmission capability and system stability study in electromechanical transient simulation in this paper. Secondly, it is showed that huge short-circuit current might be caused by using gap protected SC model, and the result of transmission capability and system stability study may deviate in that point. Finally, the comparison between the simulation and theoretical analysis shows that the adoption of linearized model could bring an acceptable result which is close to the electromagnetic transient physical characteristics of SC. The linearized model for MOV-Protected SC is proved to be accurate and effective in a real 500kV SC project, and is recommended in system stability study of SC, and fault current limiter.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.