Abstract

From failure experience on power transformers, it was very often suspected that inrush currents, occurring when energizing unloaded transformers, were reason for damage. In this paper, it was investigated how mechanical forces within the transformer coils build up under inrush compared to those occurring at short circuit. Two-dimensional and three-dimensional computer modeling for a real 268 MVA, 525/17.75 kV three-legged step up transformer was employed. The results show that inrush current peaks of 70% of the rated short circuit current cause local forces in the same order of magnitude as those at short circuit. The resulting force summed up over the high voltage coil is even three times higher. Although inrush currents normally are smaller, the forces can have similar amplitudes as those at short circuit however with longer exposure time. Therefore, care has to be taken to avoid such high inrush currents. Today controlled switching offers an elegant and practical solution.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.