Abstract
Rising wind energy integration, accompanied by a decreasing level of system inertia, requires additional sources of ancillary services. Wind turbines based on doubly fed induction generators (DFIGs) can provide inertial and primary frequency support when equipped with specific controls. This paper investigates the effect of frequency support provision by DFIGs on the small-signal stability of power systems. To this end, a modified version of the Kundur two-area test system is employed to analyze different scenarios. Wind energy generation is either added to the existing system or displaces part of the synchronous generation. Simulations show that primary frequency support tends to improve the damping of electromechanical oscillations and deteriorate it for converter control-based ones. On the other hand, the inertial response depends on the control parameters.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.