Abstract

The correct and reliable identification of SLG(single-line-to-ground) fault is the foundation of starting the fault line selection and location device in neutral un-effectively earthed system. The traditional method based on the zero sequence voltage is invalid when the fault happens with high impedance, because the zero sequence voltage in bus is small. So a new algorithm based on the variation of voltage including the zero sequence voltage and phase voltages is proposed. The algorithm is not affected by the unbalance of system, and the sensitivity and the reliability of the algorithm are considered simultaneously. The algorithm is proved effectively by the large numbers of simulations using PSCAD/EMTDC program.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.