Abstract
There is a smoothing reactor and DC filter between the inverter and the direct current line to form a boundary in the HVDC transmission system. Since this boundary presents the stop-band characteristic to the high frequency transient voltage signals, the high-frequency transient voltage signal caused by external faults through boundary will be attenuated and the signals caused by internal faults will be unchanged. In this paper, a new technique in which the S-transform is used to analyze the transient signals is proposed for distinguishing internal faults from the external faults based on the significantly difference of high-frequency transient voltage on the point of protection.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.