Abstract

The objective of this study was to assess the magnitude and balance of mechanical ventilation in the rooms of Helsinki metropolitan office buildings with different types of ventilation systems. A random sample of 50 office buildings was selected from the Building Registry. Of these buildings, the 33 that have a mechanical ventilation system were included in this study. Most office buildings in the Helsinki metropolitan area have a ducted supply and exhaust system and hot water radiator heating. Air recirculation is used in about half of the buildings which have a mechanical supply and exhaust system. The average exhaust airflow was 1.2 L/s, m2 (SD 0.73) or 17.2 L/s per person (SD 11.6). The variation of the airflows was found to be very high among the buildings, and among the rooms within the buildings. Therefore, even though the ventilation rates on average comply with the Finnish building code, it was found that many people were working in offices with airflows which were either too low or unnecessarily high.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.