Abstract
The ground source heat pump system is installed at Pamukkale University in Denizli, Turkey. The U-bend ground heat exchanger pipe length of 225 m was buried in soil at 110 m depth. In the 2007–2008 heating season, performance coefficients of the heat pump and the system were determined in the range of 2.5–4.2 and 2.03–2.66, respectively. The values of solar radiation, external temperature, relative humidity, and wind speed were measured continuously. The relations of performance coefficients of ground source heat pump according to the meteorological data including solar radiation, wind speed, relative humidity, and external temperature with this experiment was revealed exactly. The results of this study fulfill the lack in the literature.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Energy Sources, Part A: Recovery, Utilization, and Environmental Effects
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.