Abstract

The dynamic behavior of phasor measurement units (PMUs) is not only the key point to dynamic phasor algorithm improvement but also the basis for the successful implementation of PMUs in power system dynamic security monitoring and control. In this paper, the dynamic performance of PMUs is evaluated, and their dynamic behaviors are analyzed. PMUs from the four largest Chinese manufacturers are tested through the established PMU test system, and their dynamic performance is comprehensively evaluated. The dynamic behaviors of the PMUs are also analyzed. Analysis shows that the spectral leakage and the averaging effect of the discrete Fourier transform (DFT) under dynamic conditions are the key reasons that lead to their dynamic behaviors. The theoretical results are consistent with the experimental data and the simulation. Finally, to eliminate the spectral leakage, the DFT with a digital low-pass filter is adopted to obtain more precise phasor measurements.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.